Convo CVF-G3 Series High-Performance Vector Control Inverter
| Parameter | Value | Explanation | | :--- | :--- | :--- | | | 1 | Terminal command (Use external switch or keypad for start) | | F0.01 | 6 | Frequency source = PID output | | F6.00 | 1 | Enable PID function | | F6.01 | 1 | PID given target from keypad (settable) | | F6.02 | 0 | PID feedback from AI (4-20mA) | | F6.07 | 5.00 | Desired pressure (5.0 Bar). This is the setpoint. | | F6.08 | 0.50 | Proportional gain (P) – Increase for faster response | | F6.09 | 2.00 | Integral time (I) – Lower for quicker correction | | F6.10 | 0.00 | Derivative (D) – Usually 0 for pump systems | Convo Inverter Cvf G3 Manual
By following the Convo CVF-G3 manual , operators can achieve energy savings of up to in specific applications like air compressors and injection molding machines. CElectrical Kangwo Check DC fuse/breaker, battery voltage, DC connections, and
The standard LED keypad consists of:
If you want, I can: